A 3-phase 900 kVA, 3 kV / √3 kV (Δ/Y), 50 Hz transformer has primary (high voltage side) resistance per phase of 0.3 Ω and secondary (low voltage side) resistance per phase of 0.02 Ω. Iron loss of the transformer is 10 kW. The full load % efficiency of the transformer operated at unity power factor is ________ (up to 2 decimal places).
GATE 2018 EE Q.51: solution and answer
Answer and solution
ANSWER
Full-load % efficiency at unity power factor = 97.36%.
Official answer: 97.20 to 97.55Source: Official answer key, GATE 2018 EE (IIT Guwahati)
Identify winding phase voltages: primary is Δ-connected at line voltage 3 kV, so per-phase voltage = 3 kV = 3000 V; secondary is Y-connected at line voltage √3 kV, so per-phase voltage = √3 kV / √3 = 1 kV = 1000 V.
Full-load primary phase current: .
Full-load secondary phase current: .
Consistency check: phase turns ratio , and — matches, confirming the current directions and side assignment are correct.
Total full-load copper loss (sum over all three phases, both windings):
.
Total full-load losses .
Full-load output at unity power factor: .
% efficiency .
KEY IDEA
For a Δ/Y three-phase transformer, phase voltage equals line voltage on the Δ side but line voltage/√3 on the Y side; full-load phase currents on each side then follow from rated kVA = 3 × V_phase × I_phase for that side. Total copper loss is the sum of I²R loss in all three phases of both windings, and efficiency at any power factor is (output)/(output + copper loss + iron loss), with output = rated kVA × cosφ at full load.
WATCH OUT FOR
Using the line voltage as the phase voltage on the Y (secondary) side (forgetting to divide by √3), or computing copper loss for only one phase instead of multiplying by 3, both of which give a wrong current/loss and shift the efficiency outside the key range.
From the GATE 2018 EE paper. Every question of this paper · Download the full paper · All 14 Transformers questions, with notes
More Transformers questions
- GATE 2026 EE Q.17 · MCQ · 1 markA 15 kVA, 1100 V/220 V, single-phase two-winding transformer is configured as a 1.32 kV/1.1 kV…
- GATE 2026 EE Q.31 · MSQ · 1 markA 220V/12V single-phase transformer is designed for use in India and rated 100 VA at 50 Hz.
- GATE 2026 EE Q.38 · MCQ · 2 marksThree single-phase 11kV/3.3kV transformers are connected to form a three-phase transformer bank with…
- GATE 2026 IN Q.17 · MCQ · 1 markA single phase step-down transformer has a high voltage primary winding and a low voltage secondary winding.